固定氣體監(jiān)測
specifications & ordering information
alarm: 85 db (audible/visual)
functions: continuous moni-toring,
one-button
calibration, fresh-air zero cat. no. desc-ription price
cz-86392-00 o2 gas monitor $000.00
cz-86392-10 o2 gas monitor with 4 to 20 ma output 000.00
cz-86392-02 co gas monitor 000.00
cz-86392-12 co gas monitor with 4 to 20 ma output 000.00
cz-86392-04 cl2 gas monitor 000.00
cz-86392-14 cl2 gas monitor with 4 to 20 ma output 000.00
sensor range resolution alarm set points
low high
o2 0 to 30% o2 0.1% o2 19.5% o2 23.5% o2
co 0 to 500 ppm 1 ppm 3 ppm 70 ppm
cl2 0 to 100 ppm 0.1 ppm 0.5 ppm 1 ppm
airaware fixed-gas monitors
easy to use—single button calibration and fresh air zero functions!
w bright lcd shows instantaneous concentrations of gas.
w broad gas ranges with quality sensors
low/high alarm settings alert workers of potential gas hazards. basic monitor plugs easily into
any ac outlet—no installation required. models with 4 to 20 ma output have dual relays to
trigger remote alarms/ sirens, turn on fans, or shut down a process.
approval: csa
86392-00
datalogging voc detector with alarm
prevent health hazards by detecting leaks and poor air quality early
w detects acetone, methylene chloride, naphtha, trichloroethylene, and more
w ideal for laboratories, paint/print shops, and woodworking facilities
use this economical voc detector wherever solvents are present. the sensor is highly
sensitive to vocs and solvent vapors. the led bar graph displays the hazard level of gas or
vapor—green indicates normal, yellow for caution, and red for danger. an audible alarm also
alerts you to dangerous levels. responds in one minute. a rechargeable nicd battery lets you
take the detector anywhere—trace leaks to their source. features include a 0 to 2 vdc output
for datalogging and a connection for external equipment control.
catalog number desc-ription range* price
cz-86316-00 voc detector with alarm 50 to 100 ppm $000.00
*for most solvent based vocs.
display: led color bar graph
output: 0 to 2 vdc
specifications & ordering information
output: 4 to 20 ma and
5 a spdt relays
(86392-10, -12, -14
only)
power
monitors: 120 vac
monitors with output: 12 to 24 v ac/dc
dimensions:
3 1 /8"w x 5 1 /4"h x
2 5 /8"d
power: rechargeable nicd battery
with an ac adapter/charger (included)
dimensions:
2 3 /8"w x 3 1 /2"h x 1 3 /8"d
86316-00
display: backlit, 4-digit lcd
operating temperature: –4 to 140°f
(–20 to 60°c)
operating humidity: 0 to rh
specifications & ordering information
co2 transmitters
co2 monitor with output to alarm or controller
w reliable carbocap ® silicon-based ndir sensor
for accurate readings
w ip65 (nema 4) housing protects from dust and
splashes in harsh environments
rugged transmitters mount easily to any wall or flat
surface to continuously monitor co2 levels. analog
output transmits constant signal of readings. two configurable
alarm relays will transmit signal to activate remote audible/visible
alarms or shut down a process if preset co2 level is reached.
backlit, four-digit led indicates ppm or % co2 levels even in low
light conditions. abs plastic housing is ip65 (nema 4) rated for
dust and splash protection even in harsh environments. transmitter
is easy to install—simply attach the mounting plate (included) to the
wall and lock the transmitter in place. ideal for use in indoor air
quality, leak detection, fruit storage, greenhouses, and demand
controlled ventilation applications.
what’s included: probe and mounting plate.
approval: ip65 (nema 4)
compliance: en 61326-1:1997, en 50081-1, en 50082-1
catalog number range resolution accuracy price
cz-86489-00 0 to 5% 0.01% 0.02% + 2% of reading $000.00
cz-86489-02 0 to 20% 000.00
cz-86489-10 0 to 2000 ppm 1 ppm 20 ppm + 2% of reading 000.00
cz-86489-12 0 to 10,000 ppm 000.00
output
analog: 0 to 20 ma, 4 to 20 ma, 0 to 10 v
alarm relays: max 30 vac/60 vdc, 0.5 a
power: 24 vac/dc
dimensions: 4 3 /4"w x 9"h x 1 1 /4"d
86489-00
continuously
monitors co2
levels for
loss prevention
and safety
儀;控制器